FusionCol8000-C is an in-room horizontal airflow chilled water cooling solution for medium and large data centers. It supports higher water temperature and no raised floor is required. FusionCol8000-C is part of the chilled water cooling system working with chillers, water pump, and so on. Horizontal airflow, efficient fans, and heat exchanger help deliver better, more efficient cooling to data centers.
Home
Data Center Facility & Critical Power
Smart Cooling
FusionCol8000-E
Technical Specifications
Model | FusionCol8000-E260 |
Total Cooling Capacity | 260 kW |
Sensible Cooling Capacity | 260 kW |
Air Supply Mode | Horizontal flow |
Air Flow | Indoor: 60000 m3/h Outdoor: 65000 m3/h |
Input Voltage | 380~415 Vac, 50/60 Hz, 3Ph+PE |
Dimensions (W×D×H, mm) | 4700×2438×3600 |
Rated operating conditions: return air temperature 38°C, supply air temperature 25°C; outdoor dry bulb temperature 35°C, wet bulb temperature ≤ 27°C, and external static pressure (ESP) 150 Pa.