The site is located in Hangzhou, China. Before the reconstruction, the power generation efficiency is low and tenant management is difficult.
Home
Site Power Facility
CloudLi
Technical Strengths
Technical Specifications
Model | ESM-48100B1 | ESM-48100A9 | ESM-48150B1 | ESM-48150A3 | ESM-48100C1 | ESM-48100A10 | ESM-48100A11 |
Application scenario | Power backup | High-temperature cycle 45°C direct ventilation |
Power backup | Cycling | Equipment room Built-in auto extinguishing device |
Low temperature –20°C, without a heater |
High-rate 2C discharge capacity |
Dimensions (H x W x D) | 3 U x 442 mm x 396 mm | 3.6 U x 442 mm x 396 mm | 3 U x 442 mm x 560 mm | 3 U x 442 mm x 560 mm | 3.6 U x 442 mm x 396 mm | 3 U x 442 mm x 396 mm | 3 U x 442 mm x 396 mm |
Capacity | 100 Ah | 100 Ah | 150 Ah | 150 Ah | 100 Ah | 100 Ah | 100 Ah |
Number of cycles | 3500 | 8000 | 3500 | 6000 | 3500 | 3500 | 3500 |
Max. charge/discharge capability | 100 A/100 A @ 35°C | 100 A/100 A @ 35°C | 100 A/100 A @ 35°C | 100 A/100 A @ 35°C | 100 A/100 A @ 35°C | 100 A/100 A @ 35°C | 100 A/200 A @ 35°C Max. discharge power: 10 kW |
Operating temperature | Charge: 0°C to 45°C Discharge: –20°C to +45°C |
Charge: 0°C to 55°C Discharge: –20°C to +55°C |
Charge: 0°C to 45°C Discharge: –20°C to +45°C |
Charge: 0°C to 45°C Discharge: –20°C to +45°C |
Charge: 0°C to 45°C Discharge: –20°C to +45°C |
Charge: –20°C to +45°C Discharge: –20°C to +45°C |
Charge: 0°C to 45°C Discharge: –20°C to +45°C |