Recently, Huawei Digital Power's new-generation lithium battery SmartLi 5.0 successfully passed the ANSI/CAN/UL 9540A:2026 large-scale fire test and obtained the conformity certificate issued by DEKRA, a globally recognized inspection, testing, and certification organization. Huawei also became the world's first data center lithium-ion battery manufacturer to pass this standard.

The test results show that under significantly reduced external fire suppression conditions:
● The adjacent target cabinet did not catch fire after the triggered cabinet experienced about 2 hours of full thermal runaway combustion.
● The high-temperature smoke from the triggered cabinet did not cause abnormal cell valve opening in the adjacent target cabinet.
● After the flames were extinguished, the target cabinet remained structurally intact, the management and protection system could be powered on and off normally, and records such as abnormal temperature alarms were complete and exportable.
This indicates that Huawei SmartLi 5.0 does not rely on more intensive fire suppression to "keep the fire under control." Instead, it relies on its own safety architecture to isolate risks, even with reduced fire suppression conditions. It verifies the intrinsic safety of the product, not the capability of the fire suppression system.
Table 1: Comparison of third-party fire suppression trigger conditions
| Dimension | Common Industry Conditions | Huawei Test Conditions |
| Fire suppression installation height | About 4 m | 8 m |
| Fire location | Enclosed space | Semi-open large space |
| Water spray strength | About 12 L/min·m² | 3.7 L/min·m² |
| Sprinkler spacing | Within 3 m | 4.4 m × 4 m |
| Test implication | Relies more on rapid fire suppression intervention | More rigorously tests the product's own ability to prevent fire spread |
ANSI/CAN/UL 9540A:2026 raises safety thresholds, with large-scale fire testing becoming key to verifying lithium battery safety
As data centers enter the AIDC era, lithium battery backup systems are shifting from standalone devices to large-scale deployment. Once thermal runaway occurs in a battery system, customers are concerned with more than just "whether a fire will break out." They care whether the fire will spread across cabinets or cause adjacent systems to fail, whether the fire suppression system can control it effectively, and whether the incident will lead to uncontrollable system-level risks.
Against this backdrop, the sixth edition of ANSI/CAN/UL 9540A:2026 was published. Compared with previous editions, the new edition further strengthens the verification of thermal runaway propagation, large-scale fire tests, passive safety capabilities, and fire suppression boundaries. It promotes the evaluation of lithium battery safety from "cell-level safety" to "installation-level safety", and from "passing tests on devices" to "controllable, isolatable, and manageable in real deployment scenarios". For data center customers, this is the core prerequisite for lithium batteries to replace traditional lead-acid batteries at scale and be adopted in data centers.
Table 2: Key changes between the old and new editions of UL 9540A
| Dimension | Previous Editions | Sixth Edition |
| Large-scale fire test | Voluntary | Elevated to a key verification requirement |
| Fire test scope | Mainly cell-level thermal runaway verification | Installation-level large-scale fire test |
| Fire suppression triggering mode | Device-level active fire suppression may be used | Device's active fire suppression unit disabled, with reliance on passively triggered external fire suppression |
| Evaluation focus | Focus on flame spread | Focus on both flame spread and risks such as thermal runaway and valve opening in adjacent cabinets caused by high-temperature smoke |
The test results are significant in three key ways, verifying SmartLi 5.0's system-level safety capability
1. Triggered cabinet fully burned, zero spread to adjacent cabinets: thermal runaway confined within a single cabinet
The key to lithium battery safety is not just avoiding single-point failures. More importantly, it is preventing the systemic risk of a failure spreading from the cell level to the module, unit, and installation levels, and even the entire data center.
SmartLi 5.0 uses multiple safety mechanisms, including high-protection pack design, positive-pressure oxygen blocking, directed smoke exhaust, and thermal isolation. Under typical thermal runaway conditions, further thermal propagation or ignition is unlikely. To verify the protection capability in extreme scenarios, this test used full-pack overcharge combined with external forced ignition, deliberately bypassing the product's regular protection barriers. This reproduced the root cause of thermal propagation leading to fire spread in most lithium battery faults in the industry.
The test results showed that even though the triggered cabinet burned fully, the adjacent target cabinet had no fire spread, and none of its cell valves opened due to thermal runaway. This means that SmartLi 5.0 can limit extreme risks to a single cabinet, providing a critical time window for on-site handling and fire rescue.
For data center customers, the significance of this result is very straightforward: lithium battery accidents should not evolve from single-point risks to system risks. A truly safe lithium battery must be able to isolate and control the risks and prevent the risks from spreading.

2. Water-based fire suppression triggered normally in a semi-open space with a height of 8 meters: more reliable for deployment in large spaces with high ceilings
As the AIDC campus scale expands, lithium battery systems may be deployed in larger spaces, under higher ceilings, and in more complex ventilation conditions. In this case, traditional fire suppression systems face two challenges:
● Heat does not accumulate easily in large spaces, which may cause delayed detection and triggering.
● After water-based fire suppression is activated, secondary risks such as electrical short circuits and arcing may occur.
This test used a semi-open space with a height of 8 meters, which significantly increased the difficulty of triggering the fire suppression system. During the test, the water sprinkler system was triggered normally after thermal runaway occurred, and continued to spray water to extinguish the fire for about 90 minutes. More importantly, during the sprinkling process, the target cabinet did not experience short circuits, arcing, or secondary ignition due to external water spray.
This indicates that SmartLi 5.0 can control fires in complex environments and provide excellent electrical protection to avoid "the fire suppression process itself becoming a new source of risk."
For customers, this means that SmartLi 5.0 is more adaptable to deployment under high ceilings, in large spaces, and under complex fire suppression conditions. It also reduces the dependency of the lithium battery system on specific fire suppression conditions of buildings.

3. Fire controlled at a low water spray strength of 3.7 L/min·m²: The safety design simplifies the fire suppression system
The most valuable breakthrough for customers in this test is that the fire can be controlled even under low water spray strength.
In common industry test or deployment conditions, lithium battery systems usually require higher water spray strength, shorter sprinkler spacing, and stricter installation constraints to meet fire safety requirements. However, Huawei SmartLi 5.0 can effectively control the fire even under the conditions of 3.7 L/min·m² water spray strength and 4.4 m × 4 m sprinkler spacing. In addition, no secondary reignition occurred after the water supply was stopped.
The fundamental reason behind this is not that "the fire suppression configuration is stronger," but that "the product itself is safer." When the lithium battery system itself has stronger capabilities of isolating thermal runaway, preventing fire spread, and protecting electrical equipment, it need not rely excessively on large water volume, high density, and short-distance spraying. These measures serve to compensate for insufficient product safety.
This has very practical value for data center construction:
● Reduces the complexity of fire suppression design.
● Reduces restrictions on building space and sprinkler layout.
● Improves the deployment flexibility of the lithium battery system in different data center scenarios.
● Reduces customers' safety concerns about large-scale application of lithium batteries.

The safer, the fewer constraints: SmartLi 5.0 redefines the safety boundary of lithium batteries in data centers
For a long time, customers' core concerns about lithium batteries in data centers have mainly centered on three questions: whether fires will occur, whether fires will spread, and whether fire suppression can control them. The traditional solution is often to continuously improve external fire suppression conditions, using more water, longer installation distances, and stricter space restrictions to reduce risks.
However, this approach is essentially "using engineering constraints to compensate for product weaknesses." If the customer's data center does not meet the requirements in terms of floor height, space, fire suppression conditions, or installation distance, the deployment of lithium batteries will be significantly restricted.
Huawei SmartLi 5.0 has verified a different path in this test: instead of asking customers to change their data centers for lithium batteries, SmartLi 5.0 enables lithium batteries to adapt to data centers through higher intrinsic safety.
The SmartLi 5.0 has passed the ANSI/CAN/UL 9540A:2026 large-scale fire test, and achieved zero fire spread between adjacent cabinets under conditions of lower water spray strength, higher installation height, larger sprinkler spacing, and more complex space. This proves the true value of high-safety lithium batteries: ensuring safety in extreme accidents and reducing customers' fire suppression, space, and installation constraints in real-world deployments.
System-level safety underpins highly reliable power backup in the AIDC era
In the AIDC era, data centers have higher load density, higher requirements for power supply continuity, and higher loss per unit of downtime. The power backup system is more than "a backup device." It is important infrastructure that ensures continuous production of AI computing power. Only when the lithium battery system achieves full-link safety from cell, pack, and battery cabinet, to system-level fire suppression coordination can it truly support large-scale construction of AIDCs.
Huawei SmartLi 5.0 builds multiple safety capabilities from the design stage. It uses carefully selected A-grade LFP cells and safety designs such as high-protection packs, positive-pressure oxygen blocking, directed smoke exhaust, thermal isolation, and high-temperature electrical insulation. In addition, it has passed the ANSI/CAN/UL 9540A:2026 large-scale fire test to verify its safety in extreme conditions.
This test is not a simple certification, but a system-level safety verification oriented to real-world data center deployment scenarios. It proves that SmartLi 5.0 can prevent risks from spreading, ensure that adjacent systems do not fail, and ensure system traceability in the case of extreme thermal runaway and weakened fire suppression conditions.
In the future, Huawei will continue to adhere to the product concept of "safety first", verify products with higher standards, and safeguard customers' service continuity with stronger technologies. Huawei will provide safer, more reliable, and more flexible lithium battery backup solutions for global data centers and AIDC customers.
Recently, Huawei Digital Power's new-generation lithium battery SmartLi 5.0 successfully passed the ANSI/CAN/UL 9540A:2026 large-scale fire test and obtained the conformity certificate issued by DEKRA, a globally recognized inspection, testing, and certification organization. Huawei also became the world's first data center lithium-ion battery manufacturer to pass this standard.

The test results show that under significantly reduced external fire suppression conditions:
● The adjacent target cabinet did not catch fire after the triggered cabinet experienced about 2 hours of full thermal runaway combustion.
● The high-temperature smoke from the triggered cabinet did not cause abnormal cell valve opening in the adjacent target cabinet.
● After the flames were extinguished, the target cabinet remained structurally intact, the management and protection system could be powered on and off normally, and records such as abnormal temperature alarms were complete and exportable.
This indicates that Huawei SmartLi 5.0 does not rely on more intensive fire suppression to "keep the fire under control." Instead, it relies on its own safety architecture to isolate risks, even with reduced fire suppression conditions. It verifies the intrinsic safety of the product, not the capability of the fire suppression system.
Table 1: Comparison of third-party fire suppression trigger conditions
| Dimension | Common Industry Conditions | Huawei Test Conditions |
| Fire suppression installation height | About 4 m | 8 m |
| Fire location | Enclosed space | Semi-open large space |
| Water spray strength | About 12 L/min·m² | 3.7 L/min·m² |
| Sprinkler spacing | Within 3 m | 4.4 m × 4 m |
| Test implication | Relies more on rapid fire suppression intervention | More rigorously tests the product's own ability to prevent fire spread |
ANSI/CAN/UL 9540A:2026 raises safety thresholds, with large-scale fire testing becoming key to verifying lithium battery safety
As data centers enter the AIDC era, lithium battery backup systems are shifting from standalone devices to large-scale deployment. Once thermal runaway occurs in a battery system, customers are concerned with more than just "whether a fire will break out." They care whether the fire will spread across cabinets or cause adjacent systems to fail, whether the fire suppression system can control it effectively, and whether the incident will lead to uncontrollable system-level risks.
Against this backdrop, the sixth edition of ANSI/CAN/UL 9540A:2026 was published. Compared with previous editions, the new edition further strengthens the verification of thermal runaway propagation, large-scale fire tests, passive safety capabilities, and fire suppression boundaries. It promotes the evaluation of lithium battery safety from "cell-level safety" to "installation-level safety", and from "passing tests on devices" to "controllable, isolatable, and manageable in real deployment scenarios". For data center customers, this is the core prerequisite for lithium batteries to replace traditional lead-acid batteries at scale and be adopted in data centers.
Table 2: Key changes between the old and new editions of UL 9540A
| Dimension | Previous Editions | Sixth Edition |
| Large-scale fire test | Voluntary | Elevated to a key verification requirement |
| Fire test scope | Mainly cell-level thermal runaway verification | Installation-level large-scale fire test |
| Fire suppression triggering mode | Device-level active fire suppression may be used | Device's active fire suppression unit disabled, with reliance on passively triggered external fire suppression |
| Evaluation focus | Focus on flame spread | Focus on both flame spread and risks such as thermal runaway and valve opening in adjacent cabinets caused by high-temperature smoke |
The test results are significant in three key ways, verifying SmartLi 5.0's system-level safety capability
1. Triggered cabinet fully burned, zero spread to adjacent cabinets: thermal runaway confined within a single cabinet
The key to lithium battery safety is not just avoiding single-point failures. More importantly, it is preventing the systemic risk of a failure spreading from the cell level to the module, unit, and installation levels, and even the entire data center.
SmartLi 5.0 uses multiple safety mechanisms, including high-protection pack design, positive-pressure oxygen blocking, directed smoke exhaust, and thermal isolation. Under typical thermal runaway conditions, further thermal propagation or ignition is unlikely. To verify the protection capability in extreme scenarios, this test used full-pack overcharge combined with external forced ignition, deliberately bypassing the product's regular protection barriers. This reproduced the root cause of thermal propagation leading to fire spread in most lithium battery faults in the industry.
The test results showed that even though the triggered cabinet burned fully, the adjacent target cabinet had no fire spread, and none of its cell valves opened due to thermal runaway. This means that SmartLi 5.0 can limit extreme risks to a single cabinet, providing a critical time window for on-site handling and fire rescue.
For data center customers, the significance of this result is very straightforward: lithium battery accidents should not evolve from single-point risks to system risks. A truly safe lithium battery must be able to isolate and control the risks and prevent the risks from spreading.

2. Water-based fire suppression triggered normally in a semi-open space with a height of 8 meters: more reliable for deployment in large spaces with high ceilings
As the AIDC campus scale expands, lithium battery systems may be deployed in larger spaces, under higher ceilings, and in more complex ventilation conditions. In this case, traditional fire suppression systems face two challenges:
● Heat does not accumulate easily in large spaces, which may cause delayed detection and triggering.
● After water-based fire suppression is activated, secondary risks such as electrical short circuits and arcing may occur.
This test used a semi-open space with a height of 8 meters, which significantly increased the difficulty of triggering the fire suppression system. During the test, the water sprinkler system was triggered normally after thermal runaway occurred, and continued to spray water to extinguish the fire for about 90 minutes. More importantly, during the sprinkling process, the target cabinet did not experience short circuits, arcing, or secondary ignition due to external water spray.
This indicates that SmartLi 5.0 can control fires in complex environments and provide excellent electrical protection to avoid "the fire suppression process itself becoming a new source of risk."
For customers, this means that SmartLi 5.0 is more adaptable to deployment under high ceilings, in large spaces, and under complex fire suppression conditions. It also reduces the dependency of the lithium battery system on specific fire suppression conditions of buildings.

3. Fire controlled at a low water spray strength of 3.7 L/min·m²: The safety design simplifies the fire suppression system
The most valuable breakthrough for customers in this test is that the fire can be controlled even under low water spray strength.
In common industry test or deployment conditions, lithium battery systems usually require higher water spray strength, shorter sprinkler spacing, and stricter installation constraints to meet fire safety requirements. However, Huawei SmartLi 5.0 can effectively control the fire even under the conditions of 3.7 L/min·m² water spray strength and 4.4 m × 4 m sprinkler spacing. In addition, no secondary reignition occurred after the water supply was stopped.
The fundamental reason behind this is not that "the fire suppression configuration is stronger," but that "the product itself is safer." When the lithium battery system itself has stronger capabilities of isolating thermal runaway, preventing fire spread, and protecting electrical equipment, it need not rely excessively on large water volume, high density, and short-distance spraying. These measures serve to compensate for insufficient product safety.
This has very practical value for data center construction:
● Reduces the complexity of fire suppression design.
● Reduces restrictions on building space and sprinkler layout.
● Improves the deployment flexibility of the lithium battery system in different data center scenarios.
● Reduces customers' safety concerns about large-scale application of lithium batteries.

The safer, the fewer constraints: SmartLi 5.0 redefines the safety boundary of lithium batteries in data centers
For a long time, customers' core concerns about lithium batteries in data centers have mainly centered on three questions: whether fires will occur, whether fires will spread, and whether fire suppression can control them. The traditional solution is often to continuously improve external fire suppression conditions, using more water, longer installation distances, and stricter space restrictions to reduce risks.
However, this approach is essentially "using engineering constraints to compensate for product weaknesses." If the customer's data center does not meet the requirements in terms of floor height, space, fire suppression conditions, or installation distance, the deployment of lithium batteries will be significantly restricted.
Huawei SmartLi 5.0 has verified a different path in this test: instead of asking customers to change their data centers for lithium batteries, SmartLi 5.0 enables lithium batteries to adapt to data centers through higher intrinsic safety.
The SmartLi 5.0 has passed the ANSI/CAN/UL 9540A:2026 large-scale fire test, and achieved zero fire spread between adjacent cabinets under conditions of lower water spray strength, higher installation height, larger sprinkler spacing, and more complex space. This proves the true value of high-safety lithium batteries: ensuring safety in extreme accidents and reducing customers' fire suppression, space, and installation constraints in real-world deployments.
System-level safety underpins highly reliable power backup in the AIDC era
In the AIDC era, data centers have higher load density, higher requirements for power supply continuity, and higher loss per unit of downtime. The power backup system is more than "a backup device." It is important infrastructure that ensures continuous production of AI computing power. Only when the lithium battery system achieves full-link safety from cell, pack, and battery cabinet, to system-level fire suppression coordination can it truly support large-scale construction of AIDCs.
Huawei SmartLi 5.0 builds multiple safety capabilities from the design stage. It uses carefully selected A-grade LFP cells and safety designs such as high-protection packs, positive-pressure oxygen blocking, directed smoke exhaust, thermal isolation, and high-temperature electrical insulation. In addition, it has passed the ANSI/CAN/UL 9540A:2026 large-scale fire test to verify its safety in extreme conditions.
This test is not a simple certification, but a system-level safety verification oriented to real-world data center deployment scenarios. It proves that SmartLi 5.0 can prevent risks from spreading, ensure that adjacent systems do not fail, and ensure system traceability in the case of extreme thermal runaway and weakened fire suppression conditions.
In the future, Huawei will continue to adhere to the product concept of "safety first", verify products with higher standards, and safeguard customers' service continuity with stronger technologies. Huawei will provide safer, more reliable, and more flexible lithium battery backup solutions for global data centers and AIDC customers.